# Sampled Values Real-Device Evidence Pack

This document defines the minimum evidence needed before ARSVIN promotes a Sampled Values behavior from structural inference to device-observed or lab-interoperable status.

## Required inputs

Each evidence pack should contain sanitized, mutually consistent artifacts:

- device and firmware identity recorded outside protocol rules;
- SCD, CID, ICD, or IID file used for the test;
- zero-input PCAP;
- known current and voltage injection PCAPs;
- nominal system frequency;
- explicit CT, VT, or sensor conversion context;
- test-set values and tolerances;
- time-synchronization state;
- capture adapter and operating-system details;
- expected decoding, scaling, quality, continuity, RMS, and phasor results.

Device identity is evidence metadata. It must not become a hidden scaling or payload-layout rule.

## Capture cases

A first protection-stream pack should include:

1. zero input;
2. balanced nominal current;
3. balanced nominal voltage;
4. unbalanced phase values;
5. phase-angle reference cases;
6. normal sample-counter wrap;
7. one dropped sample;
8. one duplicate sample;
9. one deliberately late or out-of-order sample;
10. publisher restart or configuration-revision transition;
11. good, questionable, invalid, test, substituted, blocked, and derived quality cases where the device supports them;
12. synchronized and unsynchronized operation;
13. matching and intentionally mismatching SCL.

## Expected machine-readable files

```text
evidence/<device-id>/
source-register.md
device-context.json
expected-stream.json
expected-values.json
expected-quality.json
expected-anomalies.json
zero-input.pcap
known-current.pcap
known-voltage.pcap
sanitized-system.scd
```

Private captures may remain outside the public repository. A synthetic public fixture must reproduce every behavior protected by automated tests.

## Value domains

Expected values must state their domain explicitly:

- raw protocol count;
- primary engineering value;
- secondary-equivalent value;
- injected test-set value.

No primary-to-secondary conversion is valid without an explicit positive ratio and provenance. The report must record the ratio source and reference.

## Quality evidence

Quality is recorded per channel with:

- raw bytes;
- selected 16-bit word placement;
- validity;
- detail flags;
- process or substituted source;
- test state;
- operator-blocked state;
- profile-specific derived extension where applicable;
- resulting severity and calculation usability.

Ambiguous high-word versus low-word encoding is reported as unknown instead of guessed.

## Acceptance criteria

A real-device pack passes when:

- payload decoding is byte exact;
- channel order agrees with the bound configuration or verified profile;
- scaling provenance is explicit;
- primary and secondary values agree with the stated context and combined equipment tolerance;
- quality flags produce the expected semantic state;
- normal counter wrap is not reported as an anomaly;
- injected gaps, duplicates, and out-of-order transitions are detected;
- zero input is not visually presented as a full-scale signal;
- report JSON and Markdown preserve all relevant provenance and diagnostics;
- clean traffic produces no false blocking health state.

Passing these criteria is engineering interoperability evidence, not an accredited conformance certificate.
Original file line number Diff line number Diff line change
@@ -0,0 +1,135 @@
namespace AR.Iec61850.SampledValues.Measurements;

public enum SvMeasurementValueDomain
{
Unknown,
RawCount,
PrimaryEngineering,
SecondaryEquivalent
}

public enum SvRatioSource
{
Unknown,
Scl,
DeviceConfiguration,
Manual,
DeviceValidated
}

/// <summary>
/// Explicit instrument-transformer context. It is never inferred from vendor identity or nominal amplitude.
/// </summary>
public sealed record SvMeasurementRatio
{
public double PrimaryNominal { get; init; }
public double SecondaryNominal { get; init; }
public string Unit { get; init; } = string.Empty;
public SvRatioSource Source { get; init; } = SvRatioSource.Unknown;
public string Reference { get; init; } = string.Empty;

public bool IsValid => double.IsFinite(PrimaryNominal) &&
double.IsFinite(SecondaryNominal) &&
PrimaryNominal > 0 &&
SecondaryNominal > 0;

public double Ratio => IsValid ? PrimaryNominal / SecondaryNominal : double.NaN;

public double PrimaryToSecondary(double primaryValue)
{
EnsureValid();
return primaryValue * SecondaryNominal / PrimaryNominal;
}

public double SecondaryToPrimary(double secondaryValue)
{
EnsureValid();
return secondaryValue * PrimaryNominal / SecondaryNominal;
}

private void EnsureValid()
{
if (!IsValid)
throw new InvalidOperationException("A positive primary and secondary nominal value is required for conversion.");
}
}

public sealed record SvMeasurementDomainValue
{
public double WireValue { get; init; }
public string Unit { get; init; } = string.Empty;
public SvMeasurementValueDomain WireDomain { get; init; } = SvMeasurementValueDomain.Unknown;
public double? PrimaryValue { get; init; }
public double? SecondaryEquivalentValue { get; init; }
public SvRatioSource RatioSource { get; init; } = SvRatioSource.Unknown;
public string RatioReference { get; init; } = string.Empty;
public string Diagnostic { get; init; } = string.Empty;
}

/// <summary>
/// Produces primary and secondary-equivalent values without silently assuming a CT/VT ratio.
/// Installed-base 9-2LE engineering values are treated as primary only when the caller declares that domain.
/// </summary>
public static class SvMeasurementDomainResolver
{
public static SvMeasurementDomainValue Resolve(
double wireValue,
string unit,
SvMeasurementValueDomain wireDomain,
SvMeasurementRatio? ratio)
{
if (!double.IsFinite(wireValue))
throw new ArgumentOutOfRangeException(nameof(wireValue), "Measurement value must be finite.");

if (wireDomain is SvMeasurementValueDomain.Unknown or SvMeasurementValueDomain.RawCount)
{
return new SvMeasurementDomainValue
{
WireValue = wireValue,
Unit = unit,
WireDomain = wireDomain,
Diagnostic = "Primary and secondary values are unavailable because the wire measurement domain is not established."
};
}

if (ratio is null || !ratio.IsValid)
{
return new SvMeasurementDomainValue
{
WireValue = wireValue,
Unit = unit,
WireDomain = wireDomain,
PrimaryValue = wireDomain == SvMeasurementValueDomain.PrimaryEngineering ? wireValue : null,
SecondaryEquivalentValue = wireDomain == SvMeasurementValueDomain.SecondaryEquivalent ? wireValue : null,
Diagnostic = "Only the declared wire-domain value is available; no verified CT/VT ratio was supplied."
};
}

return wireDomain switch
{
SvMeasurementValueDomain.PrimaryEngineering => new SvMeasurementDomainValue
{
WireValue = wireValue,
Unit = unit,
WireDomain = wireDomain,
PrimaryValue = wireValue,
SecondaryEquivalentValue = ratio.PrimaryToSecondary(wireValue),
RatioSource = ratio.Source,
RatioReference = ratio.Reference,
Diagnostic = "Secondary-equivalent value was calculated from explicit ratio context."
},
SvMeasurementValueDomain.SecondaryEquivalent => new SvMeasurementDomainValue
{
WireValue = wireValue,
Unit = unit,
WireDomain = wireDomain,
PrimaryValue = ratio.SecondaryToPrimary(wireValue),
SecondaryEquivalentValue = wireValue,
RatioSource = ratio.Source,
RatioReference = ratio.Reference,
Diagnostic = "Primary value was calculated from explicit ratio context."
},
_ => throw new ArgumentOutOfRangeException(nameof(wireDomain), wireDomain, "Unsupported measurement domain.")
};
}
}